Investigation of indoor air quality in six office buildings in Chengdu, China based on field measurements

  • PDF / 2,816,598 Bytes
  • 12 Pages / 612 x 808 pts Page_size
  • 118 Downloads / 206 Views

DOWNLOAD

REPORT


Investigation of indoor air quality in six office buildings in Chengdu, China based on field measurements

Department of Environmental Science and Engineering, College of Architecture and Environment, Sichuan University, Chengdu, Sichuan Province, China

Abstract

Keywords

Indoor air pollution is of a growing concern in China. The nation’s growing urban work force spends a majority of daily time in the office, thus office indoor air quality (IAQ) can be a key determinant of worker’s wellbeing. Yet, information on office IAQ in rapidly developing southwestern China remains scarce. To address this knowledge gap, we conducted an observational study based on continuous monitoring in six office buildings in Chengdu, Sichuan Province, to investigate the concentration and variability of indoor particulate matter (PM2.5) and carbon dioxide (CO2). Hourly indoor concentrations for PM2.5 and CO2 were 0–459 μg/m3 and 375–1102 ppm, respectively, with considerable intra-building and inter-building variability. Indoor PM2.5 exhibited temporal association with ambient PM2.5, while indoor CO2 exhibits both diurnal and weekly patterns. Four out of the six buildings showed a reduction in indoor PM2.5 during work hours, suggesting functional filtration systems. However, we observed daily accumulation of indoor CO2, suggesting ineffective ventilation. Indoor PM2.5 pollution could be of health concern as all buildings experienced days when indoor PM2.5 concentration was above WHO recommendation for at least 50% of the day. Multivariate linear model predicts that every 1 μg/m3 increase in ambient PM2.5 is associated with a 0.60 μg/m3 increase in indoor PM2.5. Building-specific multivariate models show work time, weekday, outdoor PM2.5 are significantly associated with indoor PM2.5 concentration. We hope findings from this study can inform future indoor pollution mitigation strategies.

office IAQ,

1

Introduction

E-mail: [email protected]

continuous monitoring, PM2.5, carbon dioxide, urban indoor pollution

Article History Received: 27 November 2019 Revised: 20 April 2020 Accepted: 13 May 2020 © Tsinghua University Press and Springer-Verlag GmbH Germany, part of Springer Nature 2020

1997; Mendell 1993; Sangiorgi et al. 2013; Szigeti 2014). During the past few decades, urbanization in China has changed the working conditions of urban workers, with a growing number of individuals spending most of their days inside office buildings. Multiple field studies on Chinese office environment have investigated office IAQ in major cities, such as Beijing and Guangzhou, and have found that office indoor particular matter concentration was closely related to that of outdoor (Wang et al. 2016; Zhang et al. 2017). Ventilation, either natural or mechanical, plays an important role in determining pollutant concentration indoor (Wang et al. 2016; Yuan et al. 2018; Zhang et al. 2017). Other studies that focused on green buildings and energy consumption analysis further explored the health implications of office indoor environment (Bai et al. 2020; Geng e