Root Cause Failure Analysis and Mitigation of Corrosion in Seawater Injection Piping

  • PDF / 1,019,223 Bytes
  • 9 Pages / 595.276 x 790.866 pts Page_size
  • 99 Downloads / 178 Views

DOWNLOAD

REPORT


TECHNICAL ARTICLE—PEER-REVIEWED

Root Cause Failure Analysis and Mitigation of Corrosion in Seawater Injection Piping D. Ifezue . F. H. Tobins

Submitted: 5 January 2016 / Published online: 10 February 2016  ASM International 2016

Abstract This paper illustrates the methodology for performing a root cause failure analysis of corrosion anomalies reported in the low pressure section of an FPSO seawater injection piping system. Specific practical actions are recommended for mitigating the identified root causes of failure. The primary root cause of failure is oxygen corrosion due to oxygen ingress at components upstream (u/s) and downstream (d/s) of the sulfate removal (SRM) pumps. Oxygen corrosion was worsened by underdeposit corrosion caused by unavailability of coarse straining of abstracted seawater. The secondary root causes are likely due to: deterioration of graphite-filled gaskets on the flanges; occasional bisulphite overdosing; incorrectly specified oxygen scavenger; non-optimized scavenger injection rates; incorrect risk assessment; and unavailability of hypochlorination of abstracted seawater. This paper recommends that the primary and secondary root causes should be further investigated and mitigated. The less difficult but big-impact mitigations which should reduce significantly the number and severity of reported anomalies include: modeling corrosion (based on dissolved oxygen concentration inputs) with predicted velocities (V) guiding operational adjustments within the target range 2 \ V \ 10 m/s and the predicted cumulative corrosion rates used to target and optimize inspection requirements; inspecting and testing each component u/s and d/s of the SRM pump, in order to identify locations of oxygen ingress; and

D. Ifezue (&) DAIZIF Technologies Ltd, Altrincham, UK e-mail: [email protected] F. H. Tobins Department of Mechanical Engineering, University of Abuja, P.M.B 117, Abuja, Nigeria

checking deaeration performance especially possible leaks along the vacuum pump system. Results of KPIs should comply with the specified targets and be managed as part of the corrosion management system. Keywords Oxygen corrosion  Sea water injection  Root cause failure analysis

Introduction Identifying the root cause of an anomaly permits the targeting of a specific corrective measure for mitigation. For example, velocity controls may be required to reduce severe wall loss at an elbow, deadleg corrosion downstream of a PSV may indicate a passing valve which will require replacement, and so on. Mitigation of a root cause will always involve implementation of a practical action. Within a given system, the root cause of each anomaly will also be very different. The continued use of the traditional bare carbon steel for sea water injection systems compromises integrity throughout the life of field resulting in high operational maintenance costs. This is driven in part by the innate reluctance of some oil operators to trial promising technologies for new and big developments or even when replacing corroded piping. Some op